Transformer 200VA E:230/400V S:24V IP-00
Transformer 200VA E:230/400V S:24V IP-00

Transformer 800VA E:230-400V S:12V IP-00

Special manufacturing material
€129.20 Tax included

€106.78 tax excl.

Single-phase switching transformer for command, control, and general uses, with an input voltage of 230-400 Vac and an output voltage of 12 Vac. The transformer has a power output of 800 VA and an IP00 protection rating.

Reference: TR800 230-400/12

Single-phase transformer diagram 400-230 output 12

Representative image for illustrative purposes, the item supplied will correspond to the specifications indicated.

 

No queries yet, leave the first!
 

Single-phase transformer with 230-400Vac input and 12Vac output, 800VA power. Varnished transformer with IP-00 protection. Maximum current supplied is 66.67 A (apparent current).

The main application of this type of transformer is for command and control in industrial automation systems and for general applications. They are designed to power electrical devices where galvanic isolation between circuits is required. They are protected against moisture by resin impregnation.

These types of transformers are fully reversible.

Technical characteristics of the transformer:


  • Reference: TR-800 -2 / TR800 230-400/12
  • Transformer type: Single-phase
  • Transformer primary voltage: 230-400 Vac
  • Transformer secondary voltage: 12 Vac
  • Transformer rated power: 800 VA
  • Maximum intensity in the secondary (In): 66.67 A
  • Windings: Thermal class N 200ºC.
  • Insulators: Thermal class B 130ºC.
  • Frequency: 50/60 Hz.
  • Protection: IP-00.
  • Transformer test voltage:
    • 5 KV between windings.
    • 2.5 KV between windings and ground.
  • Ambient temperature: Ta= 25ºC.
  • Transformer encapsulation: varnished.
  • Transformer mounting: using screws.
  • Certificate: UNE-EN61558-2-6

Dim_transformer_monophasic_ip00

  • A: 126 mm
  • B: 135 mm
  • C: 120 mm
  • Weight: 8.2 Kg
The transformer is supplied without any type of overload protection; protection is required to prevent overloading. The indicated power and current are apparent; the active current supplied by the transformer will depend on the power factor of the connected load.
Professional use material, install in compliance with the regulations in force at the place of installation.

Questions

Be the first to ask a question about this product!

Question about the product

* Required fields
(read)

Responsible: ADAJUSA (CONSTRUCCIONES PBR, S.L.), purpose: Respond to requests for information, legitimacy: consent of the interested party, recipients: data will not be communicated to third parties, rights: Access, rectify and delete data, as well as other rights, as explained in the additional information. (read)